Space heating with dynamically heating heaters embedded in the floor is an excellent alternative to underfloor heating.
The trench heaters work almost immediately after the heating starts.
Trench heaters can heat a room independently, react quickly to any heat demand and are an easy to control heating element.
Trench heaters can heat selected, critical segments of the building, leaving others aside. Appropriate arrangement of trench heaters makes it possible to divide the space with a combination of air curtains.
Underfloor trench heating system does not limit the space, it is a great solution for aesthetic reasons.
Arrangement of contemporary interiors creates more and more complications for designers, often there is no room for wall mounted heaters, and traditional underfloor heating requires special structural preparation of the building. The best solution in such a case is trench heating.
TRENCH HEATING – APPLICATION
Trench heaters placed along glazed surfaces act as a curtain of warm air. They protect the room against the cold air flow from terraces, balconies in front of large glazed areas, in vestibules and corridors.
Heating by means of heating channels can heat selected, sensitive segments of larger rooms, omitting the others – zone heating. Appropriate arrangement of channels makes it possible to divide the space with a combination of air curtains.
Heaters placed in the underfloor heating channel do not limit the space, they are an excellent solution for heating sports facilities, sacral buildings, historic buildings, service premises, showrooms, car showrooms and others, where, apart from the heating function, the important goal is to maintain good visibility through display windows.
Trench heaters can also perform the function of auxiliary heating, being its dynamic component, used periodically, precisely during transitional periods.
Components of the trench heating system::
1. Trench platform
2. Platform framing
3. Trench heat exchanger
4. Trench trough
Floor layers::
1. Flooring
2. Glue
3. Basis
4. Raw concrete
5. Foam, insulation
6. Styrofoam
7. Damp insulation
8. Concrete
TRENCH HEAT EXCHANGER
Trench heat exchanger consist of two systems: a water system and a heat dissipation system.
The water system is made up by a copper exchanger, a pack of evenly distributed horizontal copper heat pipes that are fastened together at the ends with copper cumulative collectors. The pipe-to-collector seal is made by soldering (brazing solder).
The heat dissipation system is made up of horizontal copper pipes closely connected with vertical lamellas of aluminium sheet. These make up a dense system of pipe ribs forming numerous convection trenchs and a wavy surface of the radiator walls.
The combination of copper and aluminium is a dry connection and that is why no electrochemical corrosion occurs in it. The radiators are painted the RAL 9005 powder paint (black matt).
TRENCH TROUGH
The trench trough is made of zinc coated and powder painted sheet (RAL 9005, black matt). Trough depth 100-700 mm. Small depth troughs of the underfloor trench heating system can also be easily installed in the ceiling between the storeys.
Interior width of the trough making up the heating trench: 200 mm. The upper wider portion of the trough forms a flange, on which the framing rests and is installed. The total width of the trough flange including the framing is, respectively 250 mm.
It is possible to tailor the trough width to meet individual customer needs but only for aluminium platforms (exchange or sizing the trough to fit the existing openings in the floor, etc.).
Trench trough height adjustment system
Each trench trough is equipped with a height adjustment system to facilitate its correct positioning in relation to the target floor height. The height of the tray is adjusted with an Allen screw (ø6) – the adjustment range is from 0 to 30 mm (screws of other lengths can be used). When laying the screed, use mounting spacers or a mounting platform to avoid deformation and changes in the spacing of the framing (more in the download area – installation instructions, installation).
PLATFORM FRAME
Permanently fixed on the trough flange of the heating trench already in the unit completion phase. The upper framing edge defines the depth to which the trough is embedded in the floor. The edge must be perfectly faced with the final floor level. The platform framing is made of aluminium. It transmits the load of the platform to the ground.
The aluminium platform frame is painted or anodized in the same colour as the platform
The timber platform frame is standard painted in chestnut brown (RAL 8015). On request any colour of the platform frame is available without extra cost (RAL K7).
The border is one of two elements (the other is the platform), which remains visible after the heating set is installed in the heating channel.
Example of a trench heating set with border in colour RAL 1001 and wooden platform of slat type with spacing sleeves in colour RAL 1001.
Visually, the frame plays an equally important role as the platform. It is a pre-assembled element with the duct tray and it is at the stage of purchasing the duct heating set that you should decide on the colour of the border.
TRENCH TROUGH
Depth: 170, 270, 400, 500, 600, 700 mm
Width: 200 mm
Material: galvanised sheet metal
Finish: RAL 9005 (matte black) powder coating
Frame – outer width: 250 mm
Frame material: aluminium
TRENCH HEAT EXCHANGER
Depth: 90, 180, 270, 360, 450, 540 mm
Width: 90 mm
Material: copper tubes, aluminium lamellas
Exchanger coating: powder-coated RAL 9005 (matte black)
SET = EXCHANGER + TRENCH TROUGH WITH FRAME
Depth: 170, 270, 400, 500, 600, 700 mm
Width: 250 mm
Length – minimum: 600 mm, maximum: unlimited
Length of a single element: up to 3000 mm
Operating pressure: 1,5 MPa
Operating temperature: up to +110°С
Connection: GW ¾” Euro cone
Air vent 1/8″ socket
Supply way: from the front of the tray
Supply side: universal (reversible set)
Included in the price of the set:
- exchanger, trench trough, frame
- mounting and stabilizing set for the tray
- brass air vent
- valve cover
Technical data of SOLO type heaters
Type | Code product | Length trench trough [mm] | Depth trench trough [mm] | Width trench trough [mm] | Width frame trench trough [mm] | Power [W] 75/65/20 | Power [W] 55/45/20 | Power [W] 45/35/20 | Capacity water [l] | Weight [kg] |
---|---|---|---|---|---|---|---|---|---|---|
SOLO 170 | CASO17/600 | 600 | 170 | 200 | 250 | 182 | 92 | 53 | 0,13 | 3,28 |
SOLO 170 | CASO17/700 | 700 | 170 | 200 | 250 | 228 | 116 | 67 | 0,16 | 3,83 |
SOLO 170 | CASO17/800 | 800 | 170 | 200 | 250 | 273 | 139 | 80 | 0,18 | 4,38 |
SOLO 170 | CASO17/900 | 900 | 170 | 200 | 250 | 319 | 162 | 94 | 0,21 | 4,92 |
SOLO 170 | CASO17/1000 | 1000 | 170 | 200 | 250 | 364 | 185 | 107 | 0,24 | 5,47 |
SOLO 170 | CASO17/1100 | 1100 | 170 | 200 | 250 | 410 | 208 | 120 | 0,27 | 6,02 |
SOLO 170 | CASO17/1200 | 1200 | 170 | 200 | 250 | 455 | 231 | 133 | 0,3 | 6,56 |
SOLO 170 | CASO17/1300 | 1300 | 170 | 200 | 250 | 501 | 254 | 147 | 0,33 | 7,11 |
SOLO 170 | CASO17/1400 | 1400 | 170 | 200 | 250 | 546 | 277 | 160 | 0,36 | 7,66 |
SOLO 170 | CASO17/1500 | 1500 | 170 | 200 | 250 | 592 | 301 | 174 | 0,39 | 8,2 |
SOLO 170 | CASO17/1600 | 1600 | 170 | 200 | 250 | 637 | 323 | 187 | 0,42 | 8,75 |
SOLO 170 | CASO17/1700 | 1700 | 170 | 200 | 250 | 683 | 347 | 200 | 0,45 | 9,3 |
SOLO 170 | CASO17/1800 | 1800 | 170 | 200 | 250 | 728 | 370 | 213 | 0,47 | 9,85 |
SOLO 170 | CASO17/1900 | 1900 | 170 | 200 | 250 | 774 | 393 | 227 | 0,5 | 10,39 |
SOLO 170 | CASO17/2000 | 2000 | 170 | 200 | 250 | 819 | 416 | 240 | 0,53 | 10,94 |
SOLO 170 | CASO17/2100 | 2100 | 170 | 200 | 250 | 865 | 439 | 254 | 0,56 | 11,49 |
SOLO 170 | CASO17/2200 | 2200 | 170 | 200 | 250 | 910 | 462 | 267 | 0,59 | 12,03 |
SOLO 170 | CAS017/2300 | 2300 | 170 | 200 | 250 | 955 | 485 | 280 | 0,62 | 12,58 |
SOLO 170 | CASO17/2400 | 2400 | 170 | 200 | 250 | 1002 | 509 | 294 | 0,65 | 13,13 |
SOLO 170 | CAS017/2500 | 2500 | 170 | 200 | 250 | 1047 | 531 | 307 | 0,68 | 13,67 |
SOLO 170 | CASO17/2600 | 2600 | 170 | 200 | 250 | 1093 | 555 | 321 | 0,71 | 14,22 |
SOLO 170 | CAS017/2700 | 2700 | 170 | 200 | 250 | 1138 | 578 | 334 | 0,74 | 14,77 |
SOLO 170 | CASO17/2800 | 2800 | 170 | 200 | 250 | 1184 | 601 | 347 | 0,77 | 15,32 |
SOLO 170 | CAS017/2900 | 2900 | 170 | 200 | 250 | 1229 | 624 | 360 | 0,79 | 15,86 |
SOLO 170 | CASO17/3000 | 3000 | 170 | 200 | 250 | 1275 | 647 | 374 | 0,82 | 16,41 |
Correction coefficients for REGULUS-system trench heater SOLO
Room temperature | ||||||||
---|---|---|---|---|---|---|---|---|
tz | tp | 5 | 8 | 12 | 16 | 20 | 22 | 24 |
95 | 90 | 0.48 | 0.50 | 0.53 | 0.57 | 0.61 | 0.63 | 0.66 |
85 | 0.50 | 0.52 | 0.56 | 0.60 | 0.64 | 0.67 | 0.69 | |
80 | 0.52 | 0.54 | 0.58 | 0.63 | 0.68 | 0.70 | 0.73 | |
75 | 0.54 | 0.57 | 0.61 | 0.66 | 0.71 | 0.74 | 0.78 | |
70 | 0.57 | 0.60 | 0.64 | 0.70 | 0.76 | 0.79 | 0.83 | |
90 | 85 | 0.52 | 0.54 | 0.58 | 0.62 | 0.67 | 0.70 | 0.73 |
80 | 0.54 | 0.57 | 0.61 | 0.65 | 0.71 | 0.74 | 0.77 | |
75 | 0.56 | 0.59 | 0.64 | 0.69 | 0.75 | 0.78 | 0.82 | |
70 | 0.59 | 0.62 | 0.67 | 0.73 | 0.79 | 0.83 | 0.87 | |
65 | 0.62 | 0.66 | 0.71 | 0.77 | 0.85 | 0.89 | 0.93 | |
85 | 80 | 0.56 | 0.59 | 0.63 | 0.69 | 0.74 | 0.78 | 0.81 |
75 | 0.59 | 0.62 | 0.67 | 0.72 | 0.79 | 0.82 | 0.86 | |
70 | 0.61 | 0.65 | 0.70 | 0.76 | 0.83 | 0.88 | 0.92 | |
65 | 0.65 | 0.68 | 0.74 | 0.81 | 0.89 | 0.94 | 0.99 | |
60 | 0.68 | 0.72 | 0.79 | 0.87 | 0.96 | 1.01 | 1.07 | |
80 | 75 | 0.61 | 0.65 | 0.70 | 0.76 | 0.83 | 0.87 | 0.91 |
70 | 0.64 | 0.68 | 0.74 | 0.80 | 0.88 | 0.93 | 0.97 | |
65 | 0.68 | 0.72 | 0.78 | 0.85 | 0.94 | 0.99 | 1.05 | |
60 | 0.71 | 0.76 | 0.83 | 0.91 | 1.01 | 1.07 | 1.13 | |
55 | 0.76 | 0.81 | 0.89 | 0.98 | 1.10 | 1.17 | 1.24 | |
75 | 70 | 0.67 | 0.71 | 0.78 | 0.85 | 0.93 | 0.98 | 1.04 |
65 | 0.71 | 0.75 | 0.82 | 0.90 | 1,00 | 1.06 | 1.12 | |
60 | 0.75 | 0.80 | 0.88 | 0.97 | 1.08 | 1.14 | 1.21 | |
55 | 0.79 | 0.85 | 0.94 | 1.04 | 1.17 | 1.24 | 1.33 | |
50 | 0.85 | 0.91 | 1.01 | 1.13 | 1.28 | 1.37 | 1.47 | |
70 | 65 | 0.74 | 0.79 | 0.87 | 0.96 | 1.07 | 1.13 | 1.20 |
60 | 0.79 | 0.84 | 0.93 | 1.03 | 1.15 | 1.22 | 1.30 | |
55 | 0.83 | 0.90 | 0.99 | 1.11 | 1.25 | 1.33 | 1.43 | |
50 | 0.89 | 0.96 | 1.07 | 1.21 | 1.37 | 1.47 | 1.59 | |
45 | 0.96 | 1.04 | 1.17 | 1.33 | 1.53 | 1.65 | 1.80 | |
65 | 60 | 0.83 | 0.89 | 0.98 | 1.10 | 1.23 | 1.32 | 1.41 |
55 | 0.88 | 0.95 | 1.06 | 1.18 | 1.34 | 1.44 | 1.55 | |
50 | 0.94 | 1.02 | 1.14 | 1.29 | 1.48 | 1.59 | 1.72 | |
60 | 55 | 0.93 | 1.01 | 1.13 | 1.27 | 1.46 | 1.56 | 1.69 |
50 | 1,00 | 1.09 | 1.22 | 1.39 | 1.60 | 1.74 | 1.89 | |
45 | 1.08 | 1.17 | 1.33 | 1.53 | 1.80 | 1.96 | 2.15 | |
40 | 1.17 | 1.28 | 1.47 | 1.72 | 2.05 | 2.26 | 2.52 | |
55 | 50 | 1.07 | 1.16 | 1.32 | 1.51 | 1.76 | 1.91 | 2.09 |
45 | 1.15 | 1.26 | 1.44 | 1.67 | 1.97 | 2.16 | 2.39 | |
40 | 1.25 | 1.38 | 1.59 | 1.87 | 2.26 | 2.51 | 2.81 | |
35 | 1.37 | 1.53 | 1.79 | 2.15 | 2.67 | 3.02 | 3.47 | |
50 | 45 | 1.23 | 1.36 | 1.56 | 1.83 | 2.19 | 2.42 | 2.70 |
40 | 1.34 | 1.49 | 1.74 | 2.06 | 2.52 | 2.82 | 3.19 | |
35 | 1.48 | 1.66 | 1.96 | 2.38 | 2.99 | 3.42 | 3.97 | |
30 | 1.65 | 1.87 | 2.26 | 2.83 | 3.75 | 4.46 | 5.48 | |
45 | 40 | 1.46 | 1.62 | 1.91 | 2.30 | 2.86 | 3.23 | 3.70 |
35 | 1.60 | 1.81 | 2.16 | 2.66 | 3.41 | 3.94 | 4.65 | |
30 | 1.80 | 2.05 | 2.51 | 3.19 | 4.31 | 5.20 | 6.50 | |
40 | 35 | 1.76 | 2,00 | 2.42 | 3.03 | 3.99 | 4.69 | 5.64 |
30 | 1.97 | 2.27 | 2.82 | 3.66 | 5.09 | 6.26 | 8.03 |
Description:
tz – Flow temperature
tp – Return temperature
In the description of the heater parameters tz appears as the first value, tp as the second, and the room temperature as the third, e.g. 55/45/20
To calculate the heating power for non-standard supply parameters, divide the heating power for parameter 75/65/20 by the value read from the correction factor table.
For example, we are looking for the heating power for the S6/60 radiator for the parameter 70/50/20. The power for 75/65/20 is 922 W. In the table of correction factors, we read the coefficient for: tz = 70, tp = 50, room temperature = 20. In the table of correction coefficients read the value of the coefficient for: tz = 70, tp = 50, room temperature = 20. For these parameters the coefficient is: 1,246.
Therefore: 922/1,246 ≈740 W
VARIANT I = thermostatic valve + shut-off valve
VARIANT III = VARIANT I + the following control elements
Wireless digital ZigBee network temperature controller HTRP-RF(50) enables temperature control via CO10RF coordinating unit in offline mode or via Internet gateway in online mode (UGE600-sold separately), it can be configured to work with electronic head (TRV). When using the UGE600 internet gateway – controllable via the SALUS Smart Home app.
Features:
- built-in energy-saving TPI control algorithm
- three temperature levels
- additional functions: PARTY and HOLIDAY
- possibility to work in manual mode (permanently or temporarily)
- VP function – protects thermostatic valves against freezing
- memory backup in case of power failure
VARIANT IV = VARIANT I + the following control elements
A wireless set AURATON 200 TRA consists of an electronic head and a temperature regulator (backlit LCD display). It enables a precise and effective regulation of temperature in rooms (daily cycle). One regulator may cooperate with any number of TRA heads.
Features:
- extended vacation mode
- service switch
- calibration of temperature and time indications
- possibility of working in on/off or PWM mode
- suitable for installation on M30x1.5 radiator inserts
The platform (colloquially grill, grille, grate) is made of aluminium or wood and serves to cover the heating trench.
- transverse (the rungs are arranged across the duct axis), distances: 7, 10, or 13 mm
- the platform is the only visible component of the trench heating system
- it can be made of aluminium of wood.
- aluminium platform rungs can be placed across the trench – fix (stiff) version or roll (rollable)
- aluminium platform rungs can be placed along the trench only in fix (stiff) version
- wooden platforms – across the trench – only in roll version
- roll verison – comfortable solution, for trench maintance, transport and storage after season
- fix version best checks in case of short platforms
- large density of rungs – 7mm distance – installation on busy communication routes
Rolled platforms facilitate access to the inside of the duct during cleaning, as well as storage of the platform when it is replaced by an after-season platform, after the heating period has ended.
On request, fixed platforms and platforms with rungs along the duct axis are available.
Aluminium platform
The standard aluminium platform with rungs aligned across the channel axis is available in three rung spacing variants: 7, 10 or 13 mm (the density of the profiles in the platform affects its price).
The profiles, spacing sleeves and platform frame are supplied in pearl silver or any RAL K7 colour required by the customer (at no extra charge).
The frame of the platform, which is a pre-assembled element with the duct tray, is always, as a standard, painted the same colour as the ordered platform, provided that a complex order for the set with the platform is placed at the same time. After installing the trench heating set in the heating channel and inserting the platform, the platform with its frame will be visible in the floor plane.
The aluminium platforms are available with three rung distances: 7, 10 or 13 mm
Anodized aluminium platform
A separate method of coating aluminium platforms is anodising. It is an electrochemical process consisting in the creation of an aluminium oxide layer on the surface of aluminium platforms as a result of applying electric current to the platforms immersed in a solution of the appropriate acid (sulphuric, chromic, oxalic).
The oxide coating partially grows into the aluminium and partially covers the anodised component. Anodising increases the resistance of the platform surface to corrosion, abrasion and chemical agents. The profiles and the frame of the platforms are anodised.
There are four colour versions to choose from: C-0 – natural, C-31 – inox, C-33 – olive, C-35 – black, with three variants for the distance between the rungs: 7, 10 or 13 mm
Wooden platforms
Wooden platforms are made of high quality wood: oak and beech. They are impregnated with 50% solution of colourless nitro lacquer. On order it is possible to make platforms of non-impregnated wood. Wooden platforms are available only in rolled version. The offer includes two patterns: “bone” and “slat”. The distance between the rungs is 17 mm for the “bone” pattern and 11 mm for the “slat” pattern. The “slat” design is not available for a width of 400 mm.
Platform spacers in the “slat” design and the tub surrounds in the “slat” and “bone” designs are made of aluminium and painted chestnut brown (RAL 8015) as standard.
In the case of wooden platforms on request, both the platform sleeves and the tub surround can be painted in another RAL K7 colour (at no extra charge) or remain unpainted.
When choosing a new colour for the sockets you must also remember to specify the colour of the frame (the frame of the platform will be visible on the floor after the platform has been placed on the heating channel). The frame is the element factory-assembled with the duct tray and it is at the stage of purchasing the duct heating set that you should decide on the colour of the frame.
POST-SEASON PLATFORM
For installation outside the heating season (spring, summer, autumn) in place of the openwork platform (extends its life). It masks and protects the tray with exchanger placed in the floor against dirt. The user fills the empty post-season platform with the material of the floor surrounding the canal or in any other way. The platform can be filled in maintaining the drawing of the floor (e.g. the same arrangement of ceramic tiles or parquet staves).
The post-season platform is made of aluminium and painted in a standard pearl silver colour or, according to the customer’s wishes, in any colour from the RAL K7 palette (without an extra charge); it can also be anodised in one of the four colours offered
The post-season platform can be used as a spacer during the assembly of the trench heating set – it must be placed upside down while the screed is being poured – it also protects the trench interior against dirt during construction works.
The post-season platform is made in short lengths, up to a maximum of 1.4 metres.
It is possible to make a set of heating channels connected by corners, the angle of corners being any between 90° and 180°. The channel corner consists of a tray, frame and platform (offered only as a set).
The free space in the corner tray can be used for installation of connections, valves and controllers.
In case of the corner channel, the whole set must be ordered together as a set (i.e. with the platform, also out of season) and assembled as a set. In the production process we keep the correct dimension of all channel set elements, so that the complete channel set has the correct dimension.
When installing the tray alone without the corner platforms, a slight angle change may occur, which makes it impossible to fit the platform frame later, especially in the corner. If all the components of the system are used at the same time during installation and the installation spacers are used, there is no possibility of installation error – non-axial installation or deformation of the tray.
An additional difficulty, in the case of aluminium platforms, is the first (shortest) rung, which is a composite element with the channel frame.
Along with the order for angle modules, it is necessary to send the necessary technical drawing with the given angle. The drawing should indicate the position of the heaters and the places where the connections are to be led out, so that the openings in the baths are prepared in the desired, optimum place for the installer.
The drawing should contain the following data:
- dimensioned all elements of the corner element(s)
- the length of the corner arms on the long side
- angles of the corners
- the width of the platform
- depth of the channel
- position relative to the glazing
WARRANTY 25 YEARS!!!
REGULS®-system trench heat exchangers are covered by 25 year warranty. The warranty covers tightness of heater’s water system. The lifespan of Reguluses is comparable to lifespan of copper installation and can reach even tens of years!
TERMS OF WARRANTY
REGULUS-system s.j. seated in Bielsko-Biała on 51 Grażyńskiego street, hereby grants warranty on its products: water central unit heaters REGULUS-system.
The producer declares, that heaters REGULUS-system are manufactured according to demands of European standard EN-442.
The warranty given by producer, includes tightness of heater water system. The period of warranty is differentiated according to the place the heaters are used in:
WARRANTY 25 YEARS on trench heat exchanger (heater), installed in objects characterized by microclimate specific for residential or office areas.
WARRANTY 10 YEARS on trench heat exchanger (heater), installed in objects with above average humidity and increased sanitary regime, such as swimming pools, laundries, drying rooms, vessels, service locales or any other industrial objects, including harbor infrastructure.
WARRANTY 2 YEARS on remaining elements of the system (platforms, trenchs, frames)
- The following warranty does not hamper nor suspend buyers rights, resulting from product inconsistence with purchase agreement.
- Warranty entitlements of the client, must be implemendeted via company, in which the purchase was made. Directly at the producer, only in case, were the point of sale was liquidated.
- The Warranty begins with the date of the purchase, shown on the proof of purchase. Warranty rights, without showing the proof of purchase together with confirmed Warranty Card, will not be respected.
- In case of event covered by warranty, during period covered by warranty, the complaining User has the rights to replace the product on new of the same type.
- New product will be issued to User in place of filing a complaint, in 14 days from the date of notification. The user is bound to return the faulty product, unless the event has place during ongoing heating season. In that case, the return will occur after actual exchange.
- The producer will cover the cost of replacement of the product on new, free of faults, after receiving the appropriate bill. The value of such service must be previously agreed upon with the producer.
- Modulating valves and fans are covered by Warranties given by their producer.
- The producer is not responsible for size disparity between platform and frame caused by installation error. Platforms and frames are fit loosely ( about 1 mm). Inner platform frame width is strict and equals:For SOLO product line – 243 mm;For DUO, QUATTRO product line – 343;For DUBEL product line – 393 mm;For TRIOVENT, QUATTROVENT – 293 mm.
- The warrant of trouble-free work of trench heating system is keeping heating trenches clean.
- REGULUS®-system company reserves right to make changes to its products without prior notice.
WARRANTY DOES NOT COVER
- Defects, resulting from misuse of the product. Acceptable installation work parameters: water temperature – 110°C, working pressure – 1,5 MPa.
- Defects and inconveniences resulting from inappropriate assembly (inconsistency with assembly manual, attached with the product) and improper hydraulic adjustment of heater and pollution of water in installation.
- Defects resulting in inappropriate electrical connection or as a result of surges in power supplying installation.
- Mechanical defects.
- The warranty expires immediately, when User or anyone else, without permission, conducts modifications or repairs of REGULUS-system products.
- Warranty expires, when central heating installation, in which REGULUS-system heaters are connected is absent of mechanical filter, mounted on water feed.
- Warranty does not cover normal operational activities, connected with using the products, such as it’s connection or cleaning.
- Wooden platforms – stored or exploited in inappropriate way – in high humidity environment or without proper chemical protection of the wood. Warranty does not cover natural wearing off of the products (platforms, frames). Warranty does not cover natural work of wooden platforms.
DOES NOT AFFECT COURSE OF WARRANTY
- Setting up any kind of divisor, on outer surface of REGULUS-system heaters,
- Installing REGULUS-system heaters in open central heating stytems.
- Installing heaters in installations powered directly from city heating system, without mediation of heat exchanger.
- Periodic flushing off the water form c.h. installation, as long as other elements of the installation permit such operation, and it will not cause their corrotion.
- Cross-sections
- Technical data
Technical data of SOLO type heaters
Type Code
productLength
trench
trough
[mm]Depth
trench
trough
[mm]Width
trench
trough
[mm]Width
frame
trench
trough
[mm]Power [W]
75/65/20Power [W]
55/45/20Power [W]
45/35/20Capacity
water
[l]Weight
[kg]SOLO 170 CASO17/600 600 170 200 250 182 92 53 0,13 3,28 SOLO 170 CASO17/700 700 170 200 250 228 116 67 0,16 3,83 SOLO 170 CASO17/800 800 170 200 250 273 139 80 0,18 4,38 SOLO 170 CASO17/900 900 170 200 250 319 162 94 0,21 4,92 SOLO 170 CASO17/1000 1000 170 200 250 364 185 107 0,24 5,47 SOLO 170 CASO17/1100 1100 170 200 250 410 208 120 0,27 6,02 SOLO 170 CASO17/1200 1200 170 200 250 455 231 133 0,3 6,56 SOLO 170 CASO17/1300 1300 170 200 250 501 254 147 0,33 7,11 SOLO 170 CASO17/1400 1400 170 200 250 546 277 160 0,36 7,66 SOLO 170 CASO17/1500 1500 170 200 250 592 301 174 0,39 8,2 SOLO 170 CASO17/1600 1600 170 200 250 637 323 187 0,42 8,75 SOLO 170 CASO17/1700 1700 170 200 250 683 347 200 0,45 9,3 SOLO 170 CASO17/1800 1800 170 200 250 728 370 213 0,47 9,85 SOLO 170 CASO17/1900 1900 170 200 250 774 393 227 0,5 10,39 SOLO 170 CASO17/2000 2000 170 200 250 819 416 240 0,53 10,94 SOLO 170 CASO17/2100 2100 170 200 250 865 439 254 0,56 11,49 SOLO 170 CASO17/2200 2200 170 200 250 910 462 267 0,59 12,03 SOLO 170 CAS017/2300 2300 170 200 250 955 485 280 0,62 12,58 SOLO 170 CASO17/2400 2400 170 200 250 1002 509 294 0,65 13,13 SOLO 170 CAS017/2500 2500 170 200 250 1047 531 307 0,68 13,67 SOLO 170 CASO17/2600 2600 170 200 250 1093 555 321 0,71 14,22 SOLO 170 CAS017/2700 2700 170 200 250 1138 578 334 0,74 14,77 SOLO 170 CASO17/2800 2800 170 200 250 1184 601 347 0,77 15,32 SOLO 170 CAS017/2900 2900 170 200 250 1229 624 360 0,79 15,86 SOLO 170 CASO17/3000 3000 170 200 250 1275 647 374 0,82 16,41 - Correction coefficients
Correction coefficients for REGULUS-system trench heater SOLO
Room temperature tz tp 5 8 12 16 20 22 24 95 90 0.48 0.50 0.53 0.57 0.61 0.63 0.66 85 0.50 0.52 0.56 0.60 0.64 0.67 0.69 80 0.52 0.54 0.58 0.63 0.68 0.70 0.73 75 0.54 0.57 0.61 0.66 0.71 0.74 0.78 70 0.57 0.60 0.64 0.70 0.76 0.79 0.83 90 85 0.52 0.54 0.58 0.62 0.67 0.70 0.73 80 0.54 0.57 0.61 0.65 0.71 0.74 0.77 75 0.56 0.59 0.64 0.69 0.75 0.78 0.82 70 0.59 0.62 0.67 0.73 0.79 0.83 0.87 65 0.62 0.66 0.71 0.77 0.85 0.89 0.93 85 80 0.56 0.59 0.63 0.69 0.74 0.78 0.81 75 0.59 0.62 0.67 0.72 0.79 0.82 0.86 70 0.61 0.65 0.70 0.76 0.83 0.88 0.92 65 0.65 0.68 0.74 0.81 0.89 0.94 0.99 60 0.68 0.72 0.79 0.87 0.96 1.01 1.07 80 75 0.61 0.65 0.70 0.76 0.83 0.87 0.91 70 0.64 0.68 0.74 0.80 0.88 0.93 0.97 65 0.68 0.72 0.78 0.85 0.94 0.99 1.05 60 0.71 0.76 0.83 0.91 1.01 1.07 1.13 55 0.76 0.81 0.89 0.98 1.10 1.17 1.24 75 70 0.67 0.71 0.78 0.85 0.93 0.98 1.04 65 0.71 0.75 0.82 0.90 1,00 1.06 1.12 60 0.75 0.80 0.88 0.97 1.08 1.14 1.21 55 0.79 0.85 0.94 1.04 1.17 1.24 1.33 50 0.85 0.91 1.01 1.13 1.28 1.37 1.47 70 65 0.74 0.79 0.87 0.96 1.07 1.13 1.20 60 0.79 0.84 0.93 1.03 1.15 1.22 1.30 55 0.83 0.90 0.99 1.11 1.25 1.33 1.43 50 0.89 0.96 1.07 1.21 1.37 1.47 1.59 45 0.96 1.04 1.17 1.33 1.53 1.65 1.80 65 60 0.83 0.89 0.98 1.10 1.23 1.32 1.41 55 0.88 0.95 1.06 1.18 1.34 1.44 1.55 50 0.94 1.02 1.14 1.29 1.48 1.59 1.72 60 55 0.93 1.01 1.13 1.27 1.46 1.56 1.69 50 1,00 1.09 1.22 1.39 1.60 1.74 1.89 45 1.08 1.17 1.33 1.53 1.80 1.96 2.15 40 1.17 1.28 1.47 1.72 2.05 2.26 2.52 55 50 1.07 1.16 1.32 1.51 1.76 1.91 2.09 45 1.15 1.26 1.44 1.67 1.97 2.16 2.39 40 1.25 1.38 1.59 1.87 2.26 2.51 2.81 35 1.37 1.53 1.79 2.15 2.67 3.02 3.47 50 45 1.23 1.36 1.56 1.83 2.19 2.42 2.70 40 1.34 1.49 1.74 2.06 2.52 2.82 3.19 35 1.48 1.66 1.96 2.38 2.99 3.42 3.97 30 1.65 1.87 2.26 2.83 3.75 4.46 5.48 45 40 1.46 1.62 1.91 2.30 2.86 3.23 3.70 35 1.60 1.81 2.16 2.66 3.41 3.94 4.65 30 1.80 2.05 2.51 3.19 4.31 5.20 6.50 40 35 1.76 2,00 2.42 3.03 3.99 4.69 5.64 30 1.97 2.27 2.82 3.66 5.09 6.26 8.03 Description:
tz – Flow temperature
tp – Return temperatureIn the description of the heater parameters tz appears as the first value, tp as the second, and the room temperature as the third, e.g. 55/45/20
To calculate the heating power for non-standard supply parameters, divide the heating power for parameter 75/65/20 by the value read from the correction factor table.
For example, we are looking for the heating power for the S6/60 radiator for the parameter 70/50/20. The power for 75/65/20 is 922 W. In the table of correction factors, we read the coefficient for: tz = 70, tp = 50, room temperature = 20. In the table of correction coefficients read the value of the coefficient for: tz = 70, tp = 50, room temperature = 20. For these parameters the coefficient is: 1,246.
Therefore: 922/1,246 ≈740 W- Control
VARIANT I = thermostatic valve + shut-off valve
VARIANT III = VARIANT I + the following control elements
Wireless digital ZigBee network temperature controller HTRP-RF(50) enables temperature control via CO10RF coordinating unit in offline mode or via Internet gateway in online mode (UGE600-sold separately), it can be configured to work with electronic head (TRV). When using the UGE600 internet gateway – controllable via the SALUS Smart Home app.
Features:
- built-in energy-saving TPI control algorithm
- three temperature levels
- additional functions: PARTY and HOLIDAY
- possibility to work in manual mode (permanently or temporarily)
- VP function – protects thermostatic valves against freezing
- memory backup in case of power failure
VARIANT IV = VARIANT I + the following control elements
A wireless set AURATON 200 TRA consists of an electronic head and a temperature regulator (backlit LCD display). It enables a precise and effective regulation of temperature in rooms (daily cycle). One regulator may cooperate with any number of TRA heads.
Features:
- extended vacation mode
- service switch
- calibration of temperature and time indications
- possibility of working in on/off or PWM mode
- suitable for installation on M30x1.5 radiator inserts
- Platforms
The platform (colloquially grill, grille, grate) is made of aluminium or wood and serves to cover the heating trench.
- transverse (the rungs are arranged across the duct axis), distances: 7, 10, or 13 mm
- the platform is the only visible component of the trench heating system
- it can be made of aluminium of wood.
- aluminium platform rungs can be placed across the trench – fix (stiff) version or roll (rollable)
- aluminium platform rungs can be placed along the trench only in fix (stiff) version
- wooden platforms – across the trench – only in roll version
- roll verison – comfortable solution, for trench maintance, transport and storage after season
- fix version best checks in case of short platforms
- large density of rungs – 7mm distance – installation on busy communication routes
Rolled platforms facilitate access to the inside of the duct during cleaning, as well as storage of the platform when it is replaced by an after-season platform, after the heating period has ended.
On request, fixed platforms and platforms with rungs along the duct axis are available.Aluminium platform
The standard aluminium platform with rungs aligned across the channel axis is available in three rung spacing variants: 7, 10 or 13 mm (the density of the profiles in the platform affects its price).
The profiles, spacing sleeves and platform frame are supplied in pearl silver or any RAL K7 colour required by the customer (at no extra charge).
The frame of the platform, which is a pre-assembled element with the duct tray, is always, as a standard, painted the same colour as the ordered platform, provided that a complex order for the set with the platform is placed at the same time. After installing the trench heating set in the heating channel and inserting the platform, the platform with its frame will be visible in the floor plane.
The aluminium platforms are available with three rung distances: 7, 10 or 13 mm
Anodized aluminium platform
A separate method of coating aluminium platforms is anodising. It is an electrochemical process consisting in the creation of an aluminium oxide layer on the surface of aluminium platforms as a result of applying electric current to the platforms immersed in a solution of the appropriate acid (sulphuric, chromic, oxalic).
The oxide coating partially grows into the aluminium and partially covers the anodised component. Anodising increases the resistance of the platform surface to corrosion, abrasion and chemical agents. The profiles and the frame of the platforms are anodised.There are four colour versions to choose from: C-0 – natural, C-31 – inox, C-33 – olive, C-35 – black, with three variants for the distance between the rungs: 7, 10 or 13 mm
Wooden platforms
Wooden platforms are made of high quality wood: oak and beech. They are impregnated with 50% solution of colourless nitro lacquer. On order it is possible to make platforms of non-impregnated wood. Wooden platforms are available only in rolled version. The offer includes two patterns: “bone” and “slat”. The distance between the rungs is 17 mm for the “bone” pattern and 11 mm for the “slat” pattern. The “slat” design is not available for a width of 400 mm.
Platform spacers in the “slat” design and the tub surrounds in the “slat” and “bone” designs are made of aluminium and painted chestnut brown (RAL 8015) as standard.
In the case of wooden platforms on request, both the platform sleeves and the tub surround can be painted in another RAL K7 colour (at no extra charge) or remain unpainted.
When choosing a new colour for the sockets you must also remember to specify the colour of the frame (the frame of the platform will be visible on the floor after the platform has been placed on the heating channel). The frame is the element factory-assembled with the duct tray and it is at the stage of purchasing the duct heating set that you should decide on the colour of the frame.
POST-SEASON PLATFORM
For installation outside the heating season (spring, summer, autumn) in place of the openwork platform (extends its life). It masks and protects the tray with exchanger placed in the floor against dirt. The user fills the empty post-season platform with the material of the floor surrounding the canal or in any other way. The platform can be filled in maintaining the drawing of the floor (e.g. the same arrangement of ceramic tiles or parquet staves).
The post-season platform is made of aluminium and painted in a standard pearl silver colour or, according to the customer’s wishes, in any colour from the RAL K7 palette (without an extra charge); it can also be anodised in one of the four colours offered
The post-season platform can be used as a spacer during the assembly of the trench heating set – it must be placed upside down while the screed is being poured – it also protects the trench interior against dirt during construction works.
The post-season platform is made in short lengths, up to a maximum of 1.4 metres.- Platform corner
It is possible to make a set of heating channels connected by corners, the angle of corners being any between 90° and 180°. The channel corner consists of a tray, frame and platform (offered only as a set).
The free space in the corner tray can be used for installation of connections, valves and controllers.
In case of the corner channel, the whole set must be ordered together as a set (i.e. with the platform, also out of season) and assembled as a set. In the production process we keep the correct dimension of all channel set elements, so that the complete channel set has the correct dimension.
When installing the tray alone without the corner platforms, a slight angle change may occur, which makes it impossible to fit the platform frame later, especially in the corner. If all the components of the system are used at the same time during installation and the installation spacers are used, there is no possibility of installation error – non-axial installation or deformation of the tray.
An additional difficulty, in the case of aluminium platforms, is the first (shortest) rung, which is a composite element with the channel frame.Along with the order for angle modules, it is necessary to send the necessary technical drawing with the given angle. The drawing should indicate the position of the heaters and the places where the connections are to be led out, so that the openings in the baths are prepared in the desired, optimum place for the installer.
The drawing should contain the following data:
- dimensioned all elements of the corner element(s)
- the length of the corner arms on the long side
- angles of the corners
- the width of the platform
- depth of the channel
- position relative to the glazing
- Warranty
WARRANTY 25 YEARS!!!
REGULS®-system trench heat exchangers are covered by 25 year warranty. The warranty covers tightness of heater’s water system. The lifespan of Reguluses is comparable to lifespan of copper installation and can reach even tens of years!
TERMS OF WARRANTY
REGULUS-system s.j. seated in Bielsko-Biała on 51 Grażyńskiego street, hereby grants warranty on its products: water central unit heaters REGULUS-system.
The producer declares, that heaters REGULUS-system are manufactured according to demands of European standard EN-442.
The warranty given by producer, includes tightness of heater water system. The period of warranty is differentiated according to the place the heaters are used in:
WARRANTY 25 YEARS on trench heat exchanger (heater), installed in objects characterized by microclimate specific for residential or office areas.
WARRANTY 10 YEARS on trench heat exchanger (heater), installed in objects with above average humidity and increased sanitary regime, such as swimming pools, laundries, drying rooms, vessels, service locales or any other industrial objects, including harbor infrastructure.
WARRANTY 2 YEARS on remaining elements of the system (platforms, trenchs, frames)
- The following warranty does not hamper nor suspend buyers rights, resulting from product inconsistence with purchase agreement.
- Warranty entitlements of the client, must be implemendeted via company, in which the purchase was made. Directly at the producer, only in case, were the point of sale was liquidated.
- The Warranty begins with the date of the purchase, shown on the proof of purchase. Warranty rights, without showing the proof of purchase together with confirmed Warranty Card, will not be respected.
- In case of event covered by warranty, during period covered by warranty, the complaining User has the rights to replace the product on new of the same type.
- New product will be issued to User in place of filing a complaint, in 14 days from the date of notification. The user is bound to return the faulty product, unless the event has place during ongoing heating season. In that case, the return will occur after actual exchange.
- The producer will cover the cost of replacement of the product on new, free of faults, after receiving the appropriate bill. The value of such service must be previously agreed upon with the producer.
- Modulating valves and fans are covered by Warranties given by their producer.
- The producer is not responsible for size disparity between platform and frame caused by installation error. Platforms and frames are fit loosely ( about 1 mm). Inner platform frame width is strict and equals:For SOLO product line – 243 mm;For DUO, QUATTRO product line – 343;For DUBEL product line – 393 mm;For TRIOVENT, QUATTROVENT – 293 mm.
- The warrant of trouble-free work of trench heating system is keeping heating trenches clean.
- REGULUS®-system company reserves right to make changes to its products without prior notice.
WARRANTY DOES NOT COVER
- Defects, resulting from misuse of the product. Acceptable installation work parameters: water temperature – 110°C, working pressure – 1,5 MPa.
- Defects and inconveniences resulting from inappropriate assembly (inconsistency with assembly manual, attached with the product) and improper hydraulic adjustment of heater and pollution of water in installation.
- Defects resulting in inappropriate electrical connection or as a result of surges in power supplying installation.
- Mechanical defects.
- The warranty expires immediately, when User or anyone else, without permission, conducts modifications or repairs of REGULUS-system products.
- Warranty expires, when central heating installation, in which REGULUS-system heaters are connected is absent of mechanical filter, mounted on water feed.
- Warranty does not cover normal operational activities, connected with using the products, such as it’s connection or cleaning.
- Wooden platforms – stored or exploited in inappropriate way – in high humidity environment or without proper chemical protection of the wood. Warranty does not cover natural wearing off of the products (platforms, frames). Warranty does not cover natural work of wooden platforms.
DOES NOT AFFECT COURSE OF WARRANTY
- Setting up any kind of divisor, on outer surface of REGULUS-system heaters,
- Installing REGULUS-system heaters in open central heating stytems.
- Installing heaters in installations powered directly from city heating system, without mediation of heat exchanger.
- Periodic flushing off the water form c.h. installation, as long as other elements of the installation permit such operation, and it will not cause their corrotion.
User receiving product together with this Warranty Card accepts all of the above terms of the granted warranty.- Download